Template: Essential Energy (Typical) dynamic Network Study Requirements (<5 MVA)
Last updated: 20 Mar 2024
Country:
AU
Software required:
PSS®E
PSCAD™
Source: Typical requirements only
This gridmo template:
- Includes a selection of tests to meet the typical dynamic study requirements required to connect to Essential Energy's distribution network under Chapter 5A of the NER.
danger
To our understanding, there are no general guidelines for the power system studies required to be completed to connect a generating system to Essential Energy's distribution network.
This template has been based on requirements specified in project-specific NSR documents provided by gridmo customers.
Configuration
To use this template:
- Configure your global and scenario variables by using gridmo's Model setup template.
- Download this template using the download button above and load the template into the gridmo web-app.
- Transfer your general tab data, global variables and scenario variables across using the 'Import' buttons in the gridmo web-app.
- Response to voltage/fault disturbances:
- If your system normal SCR is >5, replace all references to
$g_max_scr
inLoop Start
Node1531
with 5. - If your system normal X/R is >10, replace all references to
$g_max_xr
inLoop Start
Node1531
with 10. - If your system N-1 SCR is >3, replace all references to
$g_min_scr
inLoop Start
Node1531
with 3. - If your system N-1 X/R is >3, replace all references to
$g_min_xr
inLoop Start
Node1531
with 3. - We have included a single multiple-fault ride-through test with the following faults. If your generating system requires a longer MFRT sequence in order to provide a more stable response, then please increase the spacing of the
SIMPLEFAULT
commands in thePSCAD™
Node1547
as required - or alternatively enter a different sequence of faults.
- If your system normal SCR is >5, replace all references to
# | Type | Duration | Fault impedance | Next fault after [sec] |
---|---|---|---|---|
1 | 1PHG | 220 ms | 0 (bolted) | 0.2 sec |
2 | PH-PH | 430 ms | 0 (bolted) | 5 sec |
3 | 1PHG | 500 ms | 70% residual | 30 sec |
4 | 2PHG | 220 ms | 60% residual | 30 sec |
5 | 1PHG | 430 ms | 60% residual | 30 sec |
6 | 1PHG | 220 ms | 0 (bolted) | N/A |
- Active power ramp rate tests
- You may need to modify the step time and simulation length of all Nodes connected to Start Node
1091
based on your generating system's active power ramp rate.
- You may need to modify the step time and simulation length of all Nodes connected to Start Node
Assumptions
- This template only includes dynamic tests - static tests are not included.
- Response to frequency disturbances:
- Our template use Automatic Access Standard (AAS) of the Australian NER S5.2.5.3 as we believe compliance with this standard is more common than Minimum Access Standards (MAS). Essential Energy's typical dynamic NSR only reference MAS. If your generating system cannot achieve AAS for frequency disturbances, please touch base with gridmo support.
- It is unclear if both PSS®E and PSCAD™ results are required for this test. The template is configured to run both PSS®E and PSCAD™ studies, however the PSCAD™ simulation is disabled by default.
- Response to voltage/fault disturbances:
- We have assumed that all faults in this section should be completed in PSCAD™ only, as all faults in the typical faults table are unbalanced faults.
- A footer in some NSR documents note that the tests under maximum SCR can be omitted if the minimum SCR fault tests show acceptable performance. For completeness, we have included both min and max SCR tests - you can disable the extra loop rows in the
Loop Start
Node1531
if desired.
Template revision history
- 15 April 2024 (v1.4.12):
- Updated to align with newest template Sticky Note format.
- 20 March 2024 (v1.4.11)
- First version released.