Warning 112 | [PSS®E] | SMIB fault not on Thévenin source branch
Relevant software:
PSS®E
Emitted message:
SIMPLEFAULT: Neither end of the specified LINE= arg is the infinite bus
VDISTURBANCE: Neither end of the specified LINE= arg is the infinite bus
Description:
This warning indicates that neither end of the line specified in the LINE=
argument of a SIMPLEFAULT
or VDISTURBANCE
command is connected to the Thévenin source (infinite bus).
Possible impact:
- This configuration may lead to voltage profiles that differ from what was specified in:
- The
SIMPLEFAULT
command'sFZ=
argument or; - The
VDISTURBANCE
command'sVPU=
orVCHANGEPU=
arguments.
- The
- This can cause this power system result to not benchmark with other power system results (unless they have an identical additional impedance in series with the Thévenin source)
Potential fixes:
- Review your PSS®E model to confirm there is a single line connecting the Thévenin voltage source's bus to the point of connection of your generating system.
- If there are additional lines:
- Check the line in the
SIMPLEFAULT, LINE=
argument is the same line as the one which defines the Thévenin equivalent resistance in your PSS®E model. - Consider removing additional lines or setting those lines to near-zero impedance (
R=0
andX=0.0001
per unit) in order to not cause error in theSIMPLEFAULT, FZ=
calculation.
- Check the line in the
- If there are additional lines and their impedance is set to be negligible, this warning can be ignored (though removing the additional lines is still recommended).
- If there are additional lines: