Warning 105 | [Various software] | Object out of service
Relevant software:
PSS®E
PowerFactory
Emitted message:
Specified object is out of service in the loaded power systems model.
Description:
This warning indicates that a specified object (such as a bus, generator, line, etc.) has an OUTPUT
command which is being used to export a value from this object, but the object is out of service in the loaded power systems model.
Possible impact:
- The value exported from this
OUTPUT
command will be set toNaN
(Not a Number) - it may raise an error if it is used as an input to another power systems software package, for example, if it is used in aSET
command in a connected PSCAD™ Node.
tip
This warning can typically be safely ignored for Static Power Flow simulations which have several contingencies and output values to a Table
Node.
Potential fixes:
- If this object should be in service for your simulation:
- Modify your PSS®E or PowerFactory model to put the object in service before running the simulation - or alternatively use a
SET, STATUS=IN
command.
- Modify your PSS®E or PowerFactory model to put the object in service before running the simulation - or alternatively use a