Skip to main content

Warning 101 | [Various software] | Thévenin source impedance abnormally high


Relevant software:

PSS®E
PowerFactory


Emitted message:

Detected abnormally large infinite generator source impedance.

Description:

This warning indicates that the Thévenin equivalent source impedance in your PSS®E or PowerFactory model is larger than recommended for SMIB studies.

danger

This warning indicates there may be an issue in your PSS®E or PowerFactory model which may impact generator performance and/or benchmarking with other software packages.

Possible impact:

  • If you are using a SET, LINE=, SCR=, XR= command, the fault level at the specified bus may be lower than specified by the command.
    • This can cause poor benchmarking with other software packages.
    • This occurs because the source impedance of the generator model (which represents the Thévenin equivalent source) is added in series with the specified impedance.
  • Voltage playback may produce voltages which differ from those specified.
    • The voltage playback location in both PSS®E and PowerFactory is behind the generator's internal impedance - such as the below.
Screenshot of PSS®E configuration window showing very high generator source impedance

Potential fixes:

To resolve this warning and fix the associated issues, change the Thévenin source impedance to be as small as possible - effectively negligible compared to the rest of the system impedance. The effect of this impedance on the fault level is minimal and voltage playback will now work as expected.

PSS®E

  • Make the Internal Zsource of the Thévenin equivalent source as large as possible. Open your PSS®E model, double click on the generator representing your Thévenin equivalent source and complete the following (see image below).
    • Change the R source (pu) parameter from its current value to the minimum recommended resistance of 0 (note - this field defaults to 0 in PSS®E so it rarely needs to be changed).
    • Change the X Source (pu) parameter from its current value (likely the PSS®E default of 1.000) to the minimum recommended reactance of 0.0001 p.u.
    • Change the Mbase (MVA) value from 100 to a higher value such as 10000.
Screenshot of PSS®E configuration window showing very high generator source impedance

PowerFactory

  • Make the Internal impedance of the AC Source block equal to 0 ohms. Open your PowerFactory model, double click on the AC Source block representing your Thévenin equivalent source and complete the following (see image below).
    • On the Load Flow tab, change Resistance, R1 to 0 ohms.
    • On the Load Flow tab, change Reactance, X1 to 0 ohms.
Screenshot of PowerFactory configuration window showing very high generator source impedance